Individual Fieldbus nodes CP2, CC2, CD2
- Camozzi
- Control
- Valves islands
- Individual Fieldbus nodes CP2, CC2, CD2
Download PDF (981,6 Kb
Interface with: Profibus-DP; CANopen and DeviceNet
Series general data
Number of digital output |
64 |
Number of digital input |
64 |
Maximum input absorption |
1,5 A |
Maximum output absorption |
3 A |
Signalling Led |
CP2: 1 led green RUN, 1 led red DIA, 1 led red BF CD2: 1 led green IO, 1 led red NS, 1 led red MS CC2: 1 led green RUN, 1 led red DIA, 1 led red BF |
FieldBus Protocol |
CP2: Profibus-DP CD2: DeviceNet CC2: CanOpen |
Maximum number of nodes |
CP2: 32/127 CD2: 64 CC2: 127 |
Maximum Baud rate |
CP2: 12 Mbit/sec CD2: 500 Kbit/sec CC2: 1 Mbit/sec |
Logical supply voltage |
24VDC (-15% / + 20%) |
Power supply voltage |
24VDC (for the tolerance, consider the total loads of the connected inputs) |
Protection |
overload and reverse polarity |
Protection class |
IP65 |
Conform with standards |
EN-61326-1 EN-61010-1 |
Operating temperature |
0-50°C |
Material |
Aluminium |
Weight |
250 g |
Dimensions |
130x68 mm |
Code
CP2
|
CP2 = Fieldbus Profibus-DP
CC2 = Fieldbus CANopen
CD2 = Fieldbus DeviceNet
|
3A
|
0 = no module
nA = numbers of modules 8 Input (n = 1÷8)
|
BC
|
0 = no module
nB = numbers of modules 4 output M12 duo
nC = numbers of modules 8 output sub-d 37 pin
nD = numbers of modules 16 output sub-d 37 pin
nE = numbers of modules 24 output sub-d 37 pin
nF = numbers of modules 32 output sub-d 37 pin
(es. 3 modules A + 2 modules E = 3A2E)
|